Về Nexans
Sản phẩm và giải pháp cáp
Hỗ trợ khách hàng
Làm việc tại Nexans
Tin tức - Báo chí
For use in railway vehicles (locomotives, trains, trolley-busses, etc.), switching stations and control panels. Installation in cable ducts, tubes and outside.
For wiring in switching stations and distribution boards up to 1.000 V, this cable is short-circuit and earth fault save.
Current-carrying capacity acc. to EN 50343 as well as VDE 0298 part 4. Serves request with regard to Hazard Level 4 acc. to EN 45545-1
1. Conductor
Flexible stranded bare copper, acc. to DIN VDE 0295/IEC 60228/HD 383 class 5, conductor wrapping optional
2. Insulation
High grade silicon type EI112 acc. to EN 50382-1
3. Separator
Foil or tape
4. Screen
Tinned copper wire braid, covering appr. 85 %
5. Separator
6. Outer sheath
High grade silicon, type EM107 acc. to EN 50382-1, oil, diesel-oil, ozone and uv resistant
Marking white:
RHEYHALON 180 (N)S2HXAFCOE 3,6/6 kV (EN) 50382-2 3600V 1x50 OF
yellow
DIN 5510 part 1 Flame protection class 1, 2, 3 and 4; BS 6853
Nominal voltage
Uo/U (Umax) = 3.6/6 (7.2) kV
Max. operating voltage in d.c. installations, one-sided earthed
Uo= 6.5 kV DC
Testing a.c. voltage (5 minutes)
U = 12.5 kV
Coupling resistance 10 kHz – 30 MHz: at Ø over braid ≤ 10 mm
≤ 150 Ω/km
Coupling resistance 10 kHz – 30 MHz: at Ø over braid > 10 mm
≤ 50 Ω/km
Conductor at normal operation
≤ 150 °C/100.000 h
≤ 180 °C/20.000 h
Conductor under short-circuit conditions (tinned)
≤ 350 °C