Về Nexans
Sản phẩm và giải pháp cáp
Hỗ trợ khách hàng
Làm việc tại Nexans
Tin tức - Báo chí
For protected installation in railway vehicles (locomotives, trains, trolley busses), switching stations and control panels. Installation in cable ducts, pipes and tubes. Current carrying capacity acc. to EN 50343 as well as VDE 0298 part 4. Serves request acc. to EN 45545-1.
1. Conductor
Flexible stranded tinned copper, class 5 acc. to DIN VDE 0295 / IEC 60228 / HD 383, conductor wrapping optional.
2. Insulation
Double layer insulation, rubber type EI110/EI109 (EM104) acc. to EN 50264-1, oil, diesel-oil, ozone and UV-resistant
e.g.: RHEYHALON VDE-Reg.-Nr. 7904 4GKW-EN 1,8/3 kV EN 50264-3-1 1800V 1x25 OM FA-Nr. ...
Black (BK)
DIN 5510 part 1: Flame protection class 1, 2, 3 and 4 BS 6853 (on request)
Nominal voltage
Uo/U (Umax) = 1,8/3 (3,6) kV
Max. operating voltage (d.c.)
Vo =2,7 kV
Testing a.c. voltage (5 minutes)
U = 6,5 kV
Conductor at normal operation
≤ 90 °C/250.000 h
≤ 120 °C/20.000 h
Overload
≤ 160 °C / 50 h
Conductor under short-circuit conditions (tinned)
≤ 200 °C
Other cross-sections on request.
Special conditions relating temperature and bending radii (e.g. by compelled guidance into cluthes, wagon transition and boogies) on request.