Applications
These instrumentation and communication cables are used to transmit analogue or digital signals in measurement and process control. They are well adapted to underground use in industrial applications, in moist areas, where chemical and mechanical protection are needed. The lead cover brings an enhanced resistance to aromatics hydrocarbons. The individual screening of each pair limits the consequence of crosstalk.
Nexans code
- 1st serie = number of pairs, triples or quads: 01 to 27
- 2nd serie = pair (IP), triple (IT), quad (IQ)
- 3rd serie = conductor 05 (1 x 0.8 mm), 09 (7 x 0.4 mm) or 15 (7 x 0.52 mm)
- 4th serie = overall screen (EG), individual screen + overall screen (EI)
- 5th serie = mechanical protection: without metal tape (SF), with steel tape (FA), with lead and steel tape (PF)
Design
Conductor:
Solid plain copper 0.50 mm² (1 x 0.80 mm) or stranded plain copper cross-section 0.88 mm² (7 x 0.40 mm) 15 mm² (7 x 0.52 mm)
Insulation:
Polyvinyl chloride (PVC)
Individual screen:
Polyester tape
Tinned copper drain wire
Aluminium/polyester tape
Individual sheath:
Polyvinyl chloride (PVC)
Overall screen:
Polyester tape
Tinned copper drain wire
Aluminium/polyester tape
Inner sheath:
Polyvinyl chloride (PVC)
Lead covering
Armour:
Paraffin-waxed crepe paper
Double steel tape
Outer sheath:
Polyvinyl chloride (PVC)
Colour: light-blue or grey
Core identification
Pair: natural - red
Triple: natural - red - blue
Blue individual sheath printed with pair/triple number
Marking
GORSE - Number of pair/triple IP/IT 05/09/15 EI PF + metric marking
|